Influence of Cooling Water Flux on the Temperature of the Vacuum Window Components of Novosibirsk Synchrotron Wigler Stations Научная публикация
Журнал |
Eurasian Journal of Mathematical and Computer Applications
ISSN: 2306-6172 |
||||
---|---|---|---|---|---|
Вых. Данные | Год: 2025, Том: 13, Номер: 2, Страницы: 105–111 Страниц : 7 DOI: 10.32523/2306-6172-2025-13-2-105-111 | ||||
Ключевые слова | cooling system, mini-channel, Siberian Circular Photon Source SKIF, Synchrotron | ||||
Авторы |
|
||||
Организации |
|
Информация о финансировании (2)
1 | Министерство науки и высшего образования Российской Федерации (с 15 мая 2018) | FWUR-2024-0040 |
2 | Министерство науки и высшего образования Российской Федерации (с 15 мая 2018) | FWNS-2021-0003 (121031800213-0)(075-00383-21-00) |
Реферат:
A 3D-modeling of the changes in the temperature field of the most important elements of the wiggler workstation vacuum windows of the Siberian Circular Photon Source SKIF synchrotron was carried out with a decrease in the pressure of cooling water and the window structure water flow rate, up to an emergency stop of the pumping station. It has been established that if the pumps are turned off, the maximum temperature in the diamond foil will rise above 372Г,В° C, which can cause recrystallization of the diamond and rupture of the foil. At the same time, boiling will not occur on the minichannel walls. However, the temperature in the liquid metal will increase by 37Г,В° C. This can significantly increase the diffusion of liquid metal components into the polycrystalline copper flange and diamond foil, which can also lead to rupture of the foil. Recommendations for preventing these accidents are presented.
Библиографическая ссылка:
Vinokurov V.V.
, Vinokurov V.A.
, Pukhovoy M.V.
, Kabov O.A.
Influence of Cooling Water Flux on the Temperature of the Vacuum Window Components of Novosibirsk Synchrotron Wigler Stations
Eurasian Journal of Mathematical and Computer Applications. 2025. V.13. N2. P.105–111. DOI: 10.32523/2306-6172-2025-13-2-105-111 WOS СКИФ ID
Influence of Cooling Water Flux on the Temperature of the Vacuum Window Components of Novosibirsk Synchrotron Wigler Stations
Eurasian Journal of Mathematical and Computer Applications. 2025. V.13. N2. P.105–111. DOI: 10.32523/2306-6172-2025-13-2-105-111 WOS СКИФ ID
Даты:
Поступила в редакцию: | 8 авг. 2024 г. |
Принята к публикации: | 20 февр. 2025 г. |
Опубликована online: | 30 июн. 2025 г. |
Идентификаторы БД:
Web of science: | WOS:001523328800009 |
СКИФ ID: | 3540 |
Цитирование в БД:
Пока нет цитирований